5 KVA Single Phase 230V 50Hz To 110V 60Hz Converter
Why buy from us?
Lorem Ipsum is simply dummy text of the printing and typesetting industry.
Ask a Question About This Product
- Stock: In Stock
- Model: HZTOHZ-G68
- Weight: 1.00
- SKU: HZTOHZ-G68
Available Options
5 kVA single phase static 50Hz/60Hz frequency converter, step down 230V (220v, 240v) to 110V (120v), step up 110V to 230V etc, adjustable output Hertz and Volts according to every equipment required specification.
Specification
| Model | HZ-50-1105 | |
| Capacity | 5 kVA | |
| Dimension | 550*400*670mm | |
| Weight | 75 kg | |
| Input | Voltage | 1 Phase 2 Wire: 110V/120V, 220V/230V/240V ± 10% (option *) |
| Frequency | 50 Hz, 60 Hz or 400 Hz ± 5% | |
| Output | Voltage, current | 110V Setting (Low grade): 0-150V, 41.6A |
| 220V Setting 0-300V (High grade): 0-300V, 20.8A | ||
| Load stabilization Rate | ≤±1% | |
| Frequency | 50Hz, 60Hz up to 400Hz (option) Note: -When the output is 400Hz, the load capacity can only reach 50% of the rated capacity. -When the output is ≤120Hz, the load capacity can reach 100% of the rated value. -You can just adjust converter output frequency in the range (40-400Hz) for 400Hz option. | |
| Frequency Stability | ≤±0.01% | |
| Harmonic Distortion | Pure Sine Wave ≤2% | |
| Frequency meter | 4 digit, digital frequency meter, resolution 0.1Hz/Step | |
| Voltmeter | 4 digit, digital voltage meter, resolution 0.1V | |
| Ammeter | 4 digit, digital ammeter, resolution 0.1A | |
| Watt meter | 4 digit, digital Watt meter, resolution 0.1W | |
| Protection | With overload, short circuit, over temperature | |
| Instantaneous power failure protection and alarm device | ||
| Working Environment | Temperature | 0 - 40 deg.℃ |
| Humidity | 0 - 90% (Non condensation) | |
| Warranty | 18 months | |
* The input voltage is factory selected.
Tips: 50 Hz transformer on 60 Hz power supply
50 Hz transformer can be used for 60 Hz operation, but reverse operation (i.e 60 Hz transformer on 50 Hz operation) will result in damaging the transformer. Theory goes, each magnetic material which could be used in a transformer’s core has a limit on how many flux lines it can handle.
The lower the operating frequency the more flux lines that are generated. Operating a transformer at 50Hz generates 20% more flux lines than at 60Hz power supply. As the number of flux lines approaches the magnetic material's limit, the heat in both the transformer's core and its coil wires increases, and under certain circumstances, unpredictably so. This can result in a transformer that exceeds safe temperature levels. Therefore, a transformer designed to run at 50Hz will simply run cooler at 60Hz. But one designed only for 60Hz may overheat if subjected to 50Hz.
i.e. from 60Hz to 50Hz, your transformer impedance will drop by 20%, therefore increasing the primary current and could saturate the core by having a higher flux. If saturation occurs, then the current flow in the primary can increase even higher and overheat.